MTOWER 2CH control instruments are a series of fully feature control systems for cooling towers.
They manage simultaneously two parameters: pH or ORP or chlorine, conductivity or inductive conductivity (to specify on order) and temperature.
Probes are not included.
They can be remotely controlled through the exclusive web management system ERMES.
- Widescreen lcd display and easy control by encoder wheel
- Current feed & bleed display
- Local & remote control
- Simultaneous multiple view for probes reading
- N.O./N.C. Levels selection,
- Inhibitor proportional dosing to wm1, wm2 or both
- gBiocide 2h proportional dosing to water meter
- Programmable biocide feed (max 1 per day), selection stop/no alarms for high/low feeding
- Working mode auto/manual/stop
- Permanent data storage with system log
- Stand-by input
- mA output (optional)
- Different working modes (on/off, impulsive proportional, proportional pwm and fixed pwm)
- Pre-bleed (educed water system conductivity before biocide dosing)
- Blow down (discharge control on conductivity values)
- Lockout (discharge valve locked for a settable time, after biocide dosage)
- Timeout (maximum discharge valve opening time)
- Programmable delay at dosing start-up (up to 99 minutes)
- PT100 temperature compensation
- Alarms and log report (hourly, daily, weekly, monthly).
MODELS(1) | MTOWER CD/PH | MTOWER CD/RH | MTOWER CD/CL | MTOWER CD/TRC |
Measuring parameters | Conductivity (or inductive conductivity) (2) pH | Conductivity (or inductive conductivity) (2) ORP | Conductivity (or inductive conductivity) (2) Chlorine | Conductivity (or inductive conductivity) (2) tracers |
Measurement and control range | 0-9999 ìS (3) 0-14 pH | 0-9999 ìS (3) 0-999 mV | 0-9999 ìS (3) chlorine different scales (4) | 0 / 9999 ìS (3) 0 / 999.9 ppm |
Compensation | temperature | temperature | temperature | temperature |